Silver Spring, MD Air Conditioning, Heating and Plumbing Services

Supreme Service Today provides Air Conditioning, Heating and Plumbing Services, Repair, Installation, Maintenance, and Tune Up in Silver Spring, MD and surrounding areas.

Check out what some of our customers are saying about Supreme Service Today.

Local Reviews
for Silver Spring, MD

Supreme Service Today Rated 4.9 out of 5 stars based on 10 customer reviews

Map of Silver Spring, MD

In Heaven!




Review of Supreme Service Today

I love the the friendly staff & sincere owner. Alex was dedicated to helping us solve our challenge with inconsistent heat. He sent a Tech out 3 times to make sure that we were completely happy with our 4 zone system. Now we have the exact combination of heat & humidity necessary to make our 11,000 square foot home comfortable, all over. Thx, Supreme Service for your supreme level of service!


Map of Silver Spring, MD

Qua




Review of Supreme Service Today


Map of Silver Spring, MD

Thorough inspection




Review of Supreme Service Today

Price quoted for replacement furnace was too high so have gone with another company. Also cost for inspection was higher than quoted. Had to pay $124 instead of $89 quoted


Map of Silver Spring, MD

Robert




Review of Supreme Service Today

Excellent service. On time arrival.


Map of Silver Spring, MD

Maintenance




Review of Supreme Service Today

Good job !


Map of Silver Spring, MD

Excellent service




Review of Supreme Service Today

Yonas called to let me know his estimated arrival time. He arrived early. He was polite, courteous and knowledgeable. He did his work efficiently and thoroughly cleaned the work area. He answered my questions clearly and succinctly. Supreme Air is fortunate to have Yonas on their team.


Map of Silver Spring, MD

Excellent service




Review of Supreme Service Today

Yonas was polite, professional and on time.


Map of Silver Spring, MD

Sting tune up




Review of Supreme Service Today


Response from Supreme Service Today:

Thank you for taking the time to submit this review. We are so glad to have provided you with such excellent service. We're looking forward to our visit in the fall to check your heating system. Thank you for being a member. Have a supreme day!


Map of Silver Spring, MD

Awesome employee




Review of Supreme Service Today

Technician Yonas Mengesha was great, explained everything he did. Would recommend to anyone based on this experience.


Map of Silver Spring, MD

Geothermal checkup




Review of Supreme Service Today


nikolayn@supremeservicetoday.com

nikolayn@supremeservicetoday.com

Up on arrival Install provided thermostat special Discount approved by Alex. System operating normal at this time.

Near Lamberton Dr, Silver Spring, MD 20902
youssefd@supremeservicetoday.com

youssefd@supremeservicetoday.com

On arrival removed tape off one register on stairway ,also adjusted master bedroom dampers .also checked all second floor dampers .also checked thermostats .unit operating normal

Near Whitehaven Rd, Silver Spring, MD 20906
tomb@supremeservicetoday.com

tomb@supremeservicetoday.com

Supply all labor and materials to install new plumbing rough in for hand sink ( supplied by others), cap water lines & drain lines for island sink that that was deleted. Also cut and cap water & drain for kitchen sink so new cabinet can be installed as part of new sink ( fixtures & sinks supplied by others) permits not included Make it so gas grill can hook up to house gas

Near Lamberton Dr, Silver Spring, MD 20902
Youssef  D.

Youssef D.

Paying on membership in authorize net

Near Pebble Run Dr, Silver Spring, MD 20902
chrisa@supremeservicetoday.com

chrisa@supremeservicetoday.com

I checked the electrical wiring and electrical systems, all are within specification, including the auxiliary heat strips. Air filter was recently replaced by the customer. I operated the unit on second stage heating mode and calculated actual heat of extraction and compared it to the printed data. As it stands now the unit is operating normal. However, there is possible refrigerant oils in the internal condensate drain pan. Customer asked me to wipe it clean so that they can look in the coming weeks to see if any more has accumulated. Customer wanted information regarding leak search cost and coil replacement cost. Customer does not want to perform leak search at this time. I also noticed the HWH expansion tank is ruptured and showed the customer. Customer paid for annual geo membership today with a check that I mobile deposited.

Near Thompson Rd, Silver Spring, MD 20905
youssefd@supremeservicetoday.com

youssefd@supremeservicetoday.com

On arrival tapped closed both upstairs registers .also checked every room and all rooms were warm ,also checked humidifier which was operating normal .also checked furnace and was operating normal . Recommend installing 2 7" manual dampers .all units are operating normal

Near Whitehaven Rd, Silver Spring, MD 20906
Yonas M.

Yonas M.

Return visit to install Ez trap and Uv lights on arrival turn the unit off from disconnect box cut the drain pipe cleaned the pipe installed Ez trap tested water is moving out normal also wired low voltage wires tested unit shut off with out any problems and install blue tube Uv lights wire low voltage wires connected with low voltage side to the transformer tested checked electrical connections checked voltage and amps checked air filter checked blower motor checked coil checked all other electrical connections unit tested unit operating normal at this time. No payment collected office collected full. DUCT CLEANING ALSO UV LIGHTS INSTALLATION AND EZ TRAP INSTALLATION

Near Lansdowne Way, Silver Spring, MD 20910
tomb@supremeservicetoday.com

tomb@supremeservicetoday.com

Redid plumbing under second-floor master bathroom 3 inch stack for toilet vanity and shower in 1000 feet turn right

Near Lamberton Dr, Silver Spring, MD 20902
Yonas M.

Yonas M.

Fall pm On 12/17/19 On arrival set unit to call for heat measured supply and return air temp measured voltage and amps inspected electrical connections checked drain checked air filter air filter needs to be replaced checked compressor capacitor checked coil checked blower motor checked EWP and LWP also water temp checked all other electrical connections unit tested unit operating normal at this time. Recommended duct cleaning uv lights installation and single or hole house surge protector installation to avoid future problems.

Near Flack St, Silver Spring, MD 20906
youssefd@supremeservicetoday.com

youssefd@supremeservicetoday.com

On arrival found system operating normal,thermostats were satisfied.checked bedroom airflow ,found 2 dampers were 25% open mi then fully opened them .unit is operating normal. Alex waived evaluation fee.

Near Whitehaven Rd, Silver Spring, MD 20906
tomb@supremeservicetoday.com

tomb@supremeservicetoday.com

Supply All labor and materials to replace main drains in floor for toilet, shower and vanity to where they come up through the second floor down main sewer stack to 6 in above kitchen floor

Near Lamberton Dr, Silver Spring, MD 20902
nikolayn@supremeservicetoday.com

nikolayn@supremeservicetoday.com

Up on arrival performed fall maintenance on 12/13/2019. Checked thermostat for operation, checked system for operation. Took readings of water pressure and delta T , took delta T in between supply and return main trunk line. Checked all electrical components. System operating normal at this time.

Near Baughman Dr, Silver Spring, MD 20906
tomb@supremeservicetoday.com

tomb@supremeservicetoday.com

Supply all labor and materials to install new plumbing rough in for hand sink ( supplied by others), cap water lines & drain lines for island sink that that was deleted. Also cut and cap water & drain for kitchen sink so new cabinet can be installed as part of new sink ( fixtures & sinks supplied by others) permits not included

Near Lamberton Dr, Silver Spring, MD 20902
youssefd@supremeservicetoday.com

youssefd@supremeservicetoday.com

On arrival cleaned evaporator coil ,tested system .unit back on normal .

Near Timberlake Dr, Silver Spring, MD 20905
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

On arrival removed defective motor i then installed new motor,tested it ,unit operating normal.also noticed oil in the drain pan recommended leak check .

Near Thompson Rd, Silver Spring, MD 20905
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

Service call on 12/02/19 On arrival set unit to call for heat nothing is comes on the inducer is not comes on also have error codes 44 which means inducer motor faults I checked electrical connections checked voltage and amps checked pressure switch also I was talk to carrier tech support I suggested to replace the inducer motor with circuit board to avoid future problems I gave option for customer also the unit is 15 years old never maintained I explained about replacing the unit customer needs quote I make quote customer he is going to decide after he is taking to his wife. Collected $124 for diagnostic fee on Check #1770

Near Luzerne Ave, Silver Spring, MD 20910
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

Install kitchen faucet garbage disposal dishwasher all parts are homeowner supplied valves are already in the cabinet for the waterlines and need to reconnect cooktop electric to be hooked up by others only thing I tested was the sink water lines and drain the touch part of the kitchen faucet would not work The cooktop garbage disposal and dishwasher did not have electric Did test gas line for leaks at connection I made

Near Riviera Terrace, Silver Spring, MD 20904
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

On arrival found system locked on high pressure,found blower motor not operating.need to replace blower motor.cutsomer didn't approve the quote at this time .

Near Thompson Rd, Silver Spring, MD 20905
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

On arrival set unit to call for heat measured supply and return air temp measured voltage and amps inspected electrical wiring ,checked thermostat,water pressure,cap,Contactor,coil which was dirty ,also checked filter.unit is operating normal at this time.

Near Timberlake Dr, Silver Spring, MD 20905
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

On arrival found system not operating found bad capacitor.also checked thermostats possiblity of zone 2 thermostat is bad but it s working at this time ,checked electrical ,checked zone panel .replaced bad cap .unit is operating normal at this time

Near Ednor Rd, Silver Spring, MD 20905
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

I replaced the Premier Board with the updated Premier Board supplied by Water Furnace. I set all dip switches to original positions and wired everything back according to wiring diagram. I cycled the unit on first and second stage heating mode and checked temperature rise and pressure drop to make sure the loop pumps were working. I retained the faulty board to return to WF. Unit operating normal.

Near Thompson Rd, Silver Spring, MD 20905
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

Last time I was here doing the maintenance I installed a Nest thermostat that the customer supplied. I had to change some common wiring inside the air handler and in doing so I inadvertently loosened the common wire for the digital humidistat. It was my fault and the call was warrantied. I called senior tech to let them know the situation. Humidistat was energized as soon as voltage was restored.

Near Pebble Run Dr, Silver Spring, MD 20902
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

Circuit board is faulty and should be replaced. Customer believes circuit board was replaced in the past. Alex to look into this on Monday and call the customer and see what they can work out. I completed a parts order form and a follow up form.

Near Thompson Rd, Silver Spring, MD 20905
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

Fall Pm on 10/22/19 On arrival set units to call for heating measured supply and return air temp measured voltage and amps inspected electrical connections checked drain and cleaned checked filters and replaced checked EWP and LWP units tested units operating normal at this time. Recommended install Uv lights for geo Unit. & Duct cleaning

Near Donna Dr, Silver Spring, MD 20905
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

Fall pm on 10/21/19 on arrival set units to call for heat measured supply and return air temp measured voltage and amps inspected electrical connections checked drain and cleaned checked filters and replaced EWP LWP units operating normal at this time.

Near Partridge Dr, Silver Spring, MD 20904
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

Fall pm on 10/21/19 on arrival set unit to call for heat measured supply and return air temp measured voltage and amps inspected electrical connections checked drain and cleaned checked filters recommend install UV lights unit operating normal at this time.

Near Somerset Ln, Silver Spring, MD 20904
Colin T.

Colin T.

Arrived onsite to inspect error code 13 on stat. Checked unit operation and inspected heat assembly. Found gas train to be shifted enough to not allow gas to shoot through tubes. Causing the rollout switch to trip. Shut down unit, shut down gas flow, and disconnected gas line. reposition gas train to shoot through tubes and reset rollout switch. Tested unit in heat test mode unit now running properly and heating with out error. Warranty per Alex.

Near Harbour Town Dr, Silver Spring, MD 20905
Colin T.

Colin T.

Performed heating pm on both systems. Replaced provided filter. Flushed out drains. Checked cleanliness of coils and blowers. Checked capacitors and contactors. Tightened electrical connections. Ran furnace heat, geo heat, and aux heat. Found igniter close to out of spec, quoting customer to replace. Found humidifier pad worn for furnace system, quoting customer humidifier service. Finally found gate valves on water heater, quoting customer to replace with ball valves. Both units operating but repairs suggested.

Near Whitehaven Rd, Silver Spring, MD 20906
Yonas M.

Yonas M.

Fall pm on 10/17/19 On arrival set unit to call for heat measured supply and return air temp measured voltage and amps inspected electrical connections checked condenser drain and cleaned checked air filter cleaned checked compressor capacitor checked coil checked EWP and LWP also checked water temp unit tested unit operating normal at this time. Recommended Uv lights installation also wet switch and voltage absorption system (Telstar) Installation.

Near Woodridge Ave, Silver Spring, MD 20902
Yonas M.

Yonas M.

HUMIDIFIER CLEANING Fall pm on 10/16/19 On arrival I replaced the unit filter I sanded the flame rectification probe and checked the burner arrangement the ignitor homes out to be in good condition set the unit to call for heat measured supply and return air temp measured voltage and amps inspected electrical connections checked drain and cleaned checked blower motor checked coil also customer needs humidifier service cleaned the humidifier pan replaced the pad checked electrical connections vacuum the drain line and cleaned unit tested unit operating normal at this time. Highly recommended duct cleaning also uv lights installation and Ez trap. Collected $156 for humidifier service on C.C

Near Lansdowne Way, Silver Spring, MD 20910
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

Up on arrival performed fall maintenance. Checked all electrical components, checked system for operation. Found blower motor assembly need new bushings , electrical air filter that we installed needed a new top filter. System working good at this time. Dispatch to follow up with customer regarding warranty coverage on bushings and electronic air cleaner

Near New Hampshire Ave, Silver Spring, MD 20904
Christopher A.

Christopher A.

I checked the gas pressure in low and high fire. I checked thermostat operation for low and high fire. I checked temperature rise in high fire and it is within manufacturing range. I checked the electrical wiring and electrical systems, all are within specification. Unit is operating normal.

Near Rocky Mt Way, Silver Spring, MD 20902
Christopher A.

Christopher A.

Install customer supplied Nest thermostat. I installed the thermostat and set it up for the type of system. I replaced the air filter. I checked the electrical wiring and electrical systems, all are within specification including the auxiliary heat strips. I forced defrost cycle at the outdoor unit. Temperature rise is 25-30 degrees. Unit operating normal.

Near Pebble Run Dr, Silver Spring, MD 20902
Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com

On arrival checked both thermostat turn circulate air on This particular home both units circulate air doing fall and winter time. heat source is in the basement area that’s not covered by supreme air. So then I checked amps, voltage, electrical connections, blower wheel is clean, evaporator coil is dirty. condenser coil is clean, electric filter is clean. Indicator light shows filter is Midway of being ready to be change at this time. I explain to customer check in about 30 days Unit operating normal at this time. I gave three estimates. To add what’s missing search protection for both air handlers and also coil cleaning for both air handlers also. I also explain the benefits of having a UV lamp On both air handlers to kill bacteria in the system.

Near Two Farm Dr, Silver Spring, MD 20904
Marc M.

Marc M.

Will have to spend about an hr in order to properly diagnose the problem within the ceiling.not responsible for ceiling. Will give over one of our partners for ceiling repair. Once I cut into ceiling found the drain to the shower pan leaking from the grate top portion. Installed a new grate silicones the edges. Told customer to refrain from using shower till tomorrow in order for caulk to set up. I tested it without chalk works great just needs a sealant for it to force the flow of water down drain.

Near Pebble Run Dr, Silver Spring, MD 20902
Marc M.

Marc M.

Upon arrival was told by customer had newly installed unit and after now has no hot water. Upon further review found pilot off at water heater. Possibly shut down gas main to house to work on hvac and didn’t know water heater was also a gas appliance. Water heater was in a separate location and in a closet in the garage. Pilot is on and unit is running.

Near Chopin Ct, Silver Spring, MD 20904
Youssef  D.

Youssef D.

On arrival found system operating normal,no whining noise .increased fan speed to 12 to check it .i didn't hear anything.unit is operating normal

Near Woodridge Ave, Silver Spring, MD 20902
Yonas M.

Yonas M.

Warranty call on arrival turn off the unit from disconnect box install new packard surge protector DTK -120/240CM+ tight up turn the unit on set the unit to call for cooling measured supply and return air temp measured voltage and amps inspected electrical connections checked all other electrical connections unit operating normal at this time. No payment collected is under warranty.

Near Timberlake Dr, Silver Spring, MD 20905
Christopher A.

Christopher A.

I called W.F. to verify operating specifications. Superheat 12-14, subcooling 10-14. Suction: 125 discharge: 335. 16 gpm. 95 ewt, 87 lwt, 30psi ewp, 24.50psi lwp. Return air temperature 74, supply 55-56. Heat of rejection 62,000-70,000 BTu/hr with eat correction factor. Unit operating normal to specification verified by W.F. I set zone control to allow second stage operation when only one zone is calling and I adjusted the weight on the blow out damper. I verified 55 degree supply air going to the master bedroom. I found no faults. That is not to say something did not happen and hopefully it doesn’t again. If something else occurs it will please call. I spoke with the service manager and was given the ok to write this call up under warranty.

Near Whitehaven Rd, Silver Spring, MD 20906
Christopher A.

Christopher A.

I transferred the badge plate and the coil bumper onto the new grille and then installed it.

Near Harbour Town Dr, Silver Spring, MD 20905
Yonas M.

Yonas M.

Spring Pm On 08/08/19 On arrival set unit to call for cooling measured supply and return air temp measured voltage and amps inspected electrical connections checked drain and cleaned checked filter cleaned check all electrical connections the indoor unit checked condenser unit outdoor checked electrical connections checked compressor capacitor checked voltage and amps measured pressure also temp and they are ideal indicating zero leaks checked coil checked all other electrical connections the outdoor unit tested unit operating normal at this time.

Near Shepperton Terrace, Silver Spring, MD 20904
Christopher A.

Christopher A.

The unit had lost most of the refrigerant charge. It had leaked out from 1 of 4 service valves. I tightened all schrader valve cores and installed new brass caps with rubber washers on 1 set of valves and on the other set I applied mechanical leak proof caps. I called Water Furnace and was given the total system charge of 127oz. I charged the unit with 7lbs and then operated the system and added more refrigerant to achieve 14 degrees subcooling and 6-8 degrees superheat. I went into the attic and had 80.2 return air temp and 59.4 supply air temperature. I checked pressure drop of the water loop and heat of rejection. Unit operating normal.

Near Whitehaven Rd, Silver Spring, MD 20906
Colin T.

Colin T.

Upon arrival I was told that geo system wasn’t keeping up at all. During diagnostics I went to condenser cube in basement and found suction line frozen. Went to attic and found entire Evap coil frozen. Checked airflow and found all dampers are open. Need to return to diagnose frozen coil. Customer asked for first apt tomorrow.

Near Whitehaven Rd, Silver Spring, MD 20906
Colin T.

Colin T.

Upon arrival I was told that system wasn’t keeping up during warmer days. I read notes of previous service calls and spoke to customer about them. Per customer ac has never been a problem, but when pm was done in spring he started noticing the system not keeping up. Per notes, fan speed was decreased, and I found it was on the lowest setting, changed back to default. Was 975cfm now 1225cfm. When inspecting AHU I found txv sensing bulb was still zip tied to the side of the coil and not on suction pipe. Shut off unit, removed all paneling, and installed txv sensing bulb on suction line for proper metering of refrigerant. I restarted system and called for ac. Found normal refrigerant pressures and temps. Normal water flow rate and heat rejection. Normal amp draw of compressor, blower, and loop pump. Also found no faults on aid tool. Called Alex and informed him of what I found and he also spoke to customer.

Near Flack St, Silver Spring, MD 20906
Christopher A.

Christopher A.

Replace left side loop pump. After I replaced the left side pump and pressurized the ground loop and burped the pumps I operated the unit. 74,000 BTU/hr heat of rejection, 12-14 degrees subcooling and 8-10 degrees superheat. 18-20 degree delta temperatures across the evaporator coil. Loop temperatures are no longer increasing with adequate wate4 flow returned.

Near Whitehaven Rd, Silver Spring, MD 20906
Colin T.

Colin T.

Upon arrival I went to unit and verified all refrigerant is out of system. Used tube cutters to cut out txv. Cleaned piping with sand paper and piped in new TXV. Brazed in both sides as well as equalizer tube. Did not remove entire tube, used coupling because of limited access. Pressure tested to 400psi nitrogen and held. No leaks and both sides equalized. Removed nitrogen and pulled vacuum to 500micron and held. Vacuum held so I added factory charge of 93.0oz of 410a. Returned power to the system and ran ac on both stages from aid tool. Verified normal refrigerant pressures and temps. Shut off system and then ran ac again from thermostat. Verified same pressures and temps. Unit is operating normal at this time.

Near Woodridge Ave, Silver Spring, MD 20902
Youssef  D.

Youssef D.

On arrival checked delta t 18 degrees.checked filter ok.checked refrigerant pressure ok.found no faults on Aurora aid tool .unit operating normal

Near Flack St, Silver Spring, MD 20906
Colin T.

Colin T.

Upon arrival we spoke to customer and he explained that system faulted the other day and hasn’t come back on, error code on thermostat. Went to system and found it faulting on low pressure. Reset unit and fault immediately appeared. Put gauges on system to find it flat. Found some oil in system but used nitrogen to trace leak. Found leak at txv and cannot he repaired. Txv needs to be replaced.

Near Woodridge Ave, Silver Spring, MD 20902
Christopher A.

Christopher A.

Reconfigure system to operate as intended. The primary issue had to do with dehumidication being set to 42%. This was causing the unit to decrease the blower speed to 1, its lowest and slowest setting in an attempt to satisfy the set point, which it could not do. I called WF tech support to ask what is the best setting, 55%, which is what I set it to. I also set blower speeds to factory specification in both heating and cooling modes. I pressurized the ground loop to 65psi and set the flow rate and checked the heat of rejection. The unit is operating normal. I did show the customer the only manual damper that could potentially be adjusted to increase airflow to the upstairs and we closed it some of the way. I advised customer to lower the thermostat set point for downstairs to see allow upstairs to cool down more. I did confirm airflow and cooling through several upstairs vents. Unit operating normal. Customer signed up for service membership. I was able to waive the dispatch fee and

Near Baughman Dr, Silver Spring, MD 20906
Youssef  D.

Youssef D.

Once we arrived we checked filter also dampers and motors, ducts checked sub cooling and added 1lb. Of 410A freon unit is operating normally at this time.

Near Whitehaven Rd, Silver Spring, MD 20906